Permit No. B2018-00516 Permit Type   NEW SFD Site Address   MALLARD CIRCLE
SONORA, CA 95370
Applied   05/02/2018 Applicant   HIGH POINT DESIGN GROUP, INC
Approved   08/31/2018 Owner   DNR ENTERPRISES INC
Issued   08/31/2018 Contractor  
Parent Permit No.   Description   TOWNHOUSE WITH ATTACHED GARAGE Unit A
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 09/26/2019SEWER CONNECTIONDan CoughlinAPPROVED

 06/19/2019ROUGH PLBGDan CoughlinCORRECTIONS(6/19/2019 10:25 AM DANC) 1. Site built dry stack retaining walls are supporting future surcharge from structures and is also greater than 4 foot in areas and requires a building permit prior approval of underground plumbing. 2. Horizontal plumbing lines are bowed and need to have consistent 1/4 inch per foot minimum fall. 3. Compaction report dated 9/25/18 does not address scaring or benching of original steep grade.

 07/02/2019REINSPECTIONDan CoughlinCANCELLEDSee Chrono

 08/13/2019UNDERGRD PLBGDan CoughlinAPPROVED W/COND(8/13/2019 10:53 AM DANC) 1. Contractor instructed to install a 2x4 plaining from bottom of rear structure footing to top of retaining wall footing to check angle of repose at next inspection.

 09/11/2019FOOTING AND FORMSDan CoughlinAPPROVED