Tuolumne County Building and Safety Division
Inspections and Results
 
Permit No. B2021-00576 Permit Type   ACCESSORY Site Address   22181 VILAS LN
SONORA, CA 95370
Applied   03/31/2021 Applicant   PLUM CONSTRUCTION INC
Approved   05/05/2021 Owner   BUNDGARD, GARY
Issued   05/06/2021 Contractor   PLUM CONSTRUCTION INC
Parent Permit No.   Description   60' X 120' METAL BUILDING
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 08/27/2021FOUNDATIONKatelyn OgburnCORRECTIONS(8/27/2021 2:37 PM KO) DO NOT POUR 1. Install rebar per plans including hairpins and 18" rebar grid with 6" concrete slab OR Submit engineering for alteration from plan on right side of building. (8/30/2021 11:00 AM MC) RECEIVED ENGINEERING PER KO REQUEST. ENGINEERING IN WITH APPROVED PLANS AND CONTRACTOR HAS APPROVED SET ON SITE.

 09/30/2021SLABSRick BarrieauAPPROVEDSTEEL

 01/14/2022ROUGH ELECKatelyn OgburnAPPROVEDtrench(1/14/2022 10:31 AM KO) noted on permit: 1 plug, 1 light, and subpanel. Trench from metal building to fire hydrant at corner of solar.

 01/18/2022FINALDan CoughlinCORRECTIONS(1/18/2022 10:45 AM DANC) 1. Provide special inspection documentation for 3000psi concrete. 2. Grade away from foundation 5% for 10 foot prior to drain rock placement.

 01/20/2022FINALBrian BellAPPROVED