09/25/2021
8:42 AM
Tuolumne County Building and Safety Division
Inspections and Results
 
Permit No. B2021-01361 Permit Type   ELECTRICAL SERVICE Site Address   22591 CONFIDENCE RD
TWAIN HARTE, CA 95383
Applied   07/20/2021 Applicant   PH ELECTRIC
Approved   07/20/2021 Owner   LO VINE, WINNIE M TR
Issued   07/20/2021 Contractor   PH ELECTRIC
Parent Permit No.   Description   INSTALL18KW GENERATOR + ELECTRIC PANEL CHANGE OUT
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

 07/22/2021GAS PIPINGRick BarrieauCORRECTIONSGAS PRESSURE TEST(7/22/2021 9:49 AM RB) Needs 10 psi for 15 min.

 07/28/2021REINSPECTIONRick BarrieauAPPROVED

 08/06/2021FINALDan CoughlinCORRECTIONS(8/6/2021 1:46 PM DANC) 1. Line side tap done without inspection: have PG&E pull meter and call for County inspection of connections behind meter. 2. Provide line diagram of electric panels and wiring for County Approval: dcoughlin@co.tuolumne.ca.us. 3. New neutral and ground not allowed on same lug in main panel. 4. Neutral bar shall float and ground bar shall not in subpanel. 5. Complete paint/protect of black iron gas line at riser.

 09/14/2021PERMANENT POWERKatelyn OgburnCORRECTIONS& PER POWER(9/14/2021 11:54 AM KO) not ready at noon. Doing panel changeout rather than reinspection of Final. Will stop by at end of day, 3-5pm (9/14/2021 5:16 PM KO) Generator correction items were not inspected. Please address previous items and call for reinspection. 125 Amp OH temp power 1. Grounding electrode conductor to be continuous in one piece from main panel to ground rod. 2. Paint/prime raw wood around new main service panel.

 09/21/2021FINALDan CoughlinAPPROVED(9/21/2021 12:00 PM DANC) Smoke form okay.

FINAL